RONAN Engineering

VISUAL ANNUNCIATOR WITH INTEGRAL LOGIC

SERIES X11SN, X12

The X11SN multipoint systems feature alarm modules with on-board alarm logicAnnun1.gif (9012 bytes) for single, dual, triple, and quad windows, lit by Light Emitting Diodes (LED's) or two incandescent lamps. The X12 system provides for single point alarm logic modules driving lamp or LED based window display from single to quad arrays per mechanical modules.

The alarm logic, based on CMOS or microprocessor, is designed to generate any of the ISA 18.1 alarm sequences and a large number of custom sequences. The logic is designed to meet IEEE 472 Surge Withstand Test and high noise immunity requirements.

On-board options, such as optoisolation for live AC or DC voltages, analog or transistor inputs, time delays, selectable dual audible, ringback audible, short circuit proof lamp drivers, lamp dim, and dual colors are available.

Auxiliary function modules, such as auxiliary contact modules, reflash modules, loss of motion detector and analog input modules may be integrated individually or in combination into the various systems.

X11SN Solid State Annunciator GENERAL SPECIFICATIONS

System Voltage:
Lamps, Logic - 24 Vdc ± 20%
Field Contacts - 24 Vdc, 48 Vdc, 125 Vdc, 115 Vac, or 240 Vac
Power Source (System External):
Power Supply - 115 Vac 50/60 Hz; 240 Vac 50/60 Hz
Converter - 24 Vdc, 48 Vdc, or 125 Vdc
Temperature Range: Operating 0° to 60° C (32° to 140° F)
                          Storage -40° to +60° C (-40° to +140° F)
Inputs:
Contact - Dry or Live; Normally Open / Normally Closed; Field Selectable
Interrogation Voltage - 24 Vdc, 48 Vdc, 125 Vdc, 115 Vac, or 240 Vac
Response Time: 10 milliseconds
Surge Withstand Capability (SWC):
Input and Power Connection - IEEE 472-1974 and ANSI/IEEE C37-90-1978
Outputs:
Visual - Fast Flash, Slow Flash, Steady ON, Intermittent Fast Flash
Audible - Dual, Selectable by Window
Auxiliary Relays - Form C, Selectable Form A or B; Normally Not Energized or Normally Energized
Contact Rating - General Purpose: 3 Amp. @ 28 Vdc; 2 Amp. @ 115Vac
Common System Relay - Selectable Retransmit or Common Trouble Alarm
Contact Rating - General Purpose and Hermetically Sealed; 10 Amp. @ 28 Vdc, 10 Amp. @ 115 Vac
Controls:
Momentary Push Button - Integral or Remote; Single Pole, Normally Open; +V Switched;
Silence, Acknowledge, Reset, Test
System Size:
Basic Cabinet Module - 3.5 inch (89 mm) x 3.5 inch (89 mm); For detailed sizes see Sales Brochure.
System Weight: Per Cabinet Module - 5 pounds (2.3 kg), not including Power Supply

Information Request Form

Select the items that apply, and then let us know how to contact you.

Send product literature
Send company literature
Have a salesperson contact me

Name
Title
Company
Address
E-mail
Phone

Questions or comments about this web site should be sent to sales@whcinc.com.
Last modified: 03/31/09